What size generator do I need for a 75 hp motor?

What size generator do I need for a 75 hp motor?

Rule of Thumb

Electric Motor Size Minimum Generator Req’d (KVA) by Starting Method
HP KW D.O.L to KVA Size (Note 1)
25 19.6 60.5
30 22 75
40 30 100

How many kilowatts does a 100 hp motor use?

This 100-horsepower centrifugal pump motor, if fully loaded, should be consuming nearly 80,000 watts (80 kW).

What kVA generator do I need to run a motor?

The Full load input of the motor assuming an efficiency of 80\% and a power factor of 0.8 lag the KVA input at FL = 20 x 0.75 / (0.8 x 0.8) = 23.44 KVA. If the motor is started with FL on the shaft and a starter to limit the starting current, may be you will require about 40 to 45 KVA generator.

READ ALSO:   What is the reason for religion?

What size generator do I need to start a 240 volt motor?

The generator must produce 31 Amps at 240 Volts, to safely start this motor. Multiply 31 amps x 240 Volts = 7400 Watts or 7.5 KW generator size. Sizing a generator for three phase motor starting LRA : The formula is: Motor HP x KVA per HP x (1000 / (Volts x 1.73)) = LRA.

How do you size a generator for a 3 phase motor?

Multiply 31 amps x 240 Volts = 7400 Watts or 7.5 KW generator size. Sizing a generator for three phase motor starting LRA : The formula is: Motor HP x KVA per HP x (1000 / (Volts x 1.73)) = LRA.

What size generator do I need for a 31 LRA motor?

7.425×4.167 = 30.9 = 31 LRA. The generator must produce 31 Amps at 240 Volts, to safely start this motor. Multiply 31 amps x 240 Volts = 7400 Watts or 7.5 KW generator size. Sizing a generator for three phase motor starting LRA : The formula is: Motor HP x KVA per HP x (1000 / (Volts x 1.73)) = LRA. Example: A 20 HP Code G motor connected to 460